Technical Documents & Engineering Support

Refrigeration engineering documents, selection guides and troubleshooting references written by the CHANGXUE engineering department — plus a direct line to our support engineers whenever a system needs attention.

10Technical documents
24 hSupport hotline
48 hSpare-parts dispatch
Technical Documents

Refrigeration Technical Library

Free to read online or download as a PDF. Covering cold-room design, equipment selection, refrigerant choice, commissioning, maintenance and fault-finding. Every document carries a document number and revision so it can be quoted directly in a service report.

Loading technical documents…

Technical Support

Support That Keeps Your Cold Chain Running

Whether it is a compressor tripping at 3 a.m. or a room that will not pull down, our engineers work from your readings, not from guesswork. Send us the numbers and we will tell you what to check next.

How support works

1

Contact us

Call the hotline or send the form below with your equipment model, a description of the fault and your current readings — suction and discharge pressure, room temperature, superheat and subcooling.

Reply within 2 hours
2

Remote diagnosis

An engineer works through the fault tree with you using the values you send, and confirms whether the cause is refrigerant charge, airflow, defrost, control settings or a component failure.

Same working day
3

Repair or part supply

We guide your technician through the repair, or supply the replacement component. Stock items are packed and dispatched quickly so the room is back online with minimum product risk.

Stock parts dispatched in 48 h
4

Verification follow-up

After the repair we compare performance against the commissioning values and confirm the fault has not simply moved elsewhere. A follow-up check confirms the fix held.

Follow-up within 7 days

Contact technical support

ChannelResponse commitmentAvailability
Phone / WhatsAppAnswer within 2 hours24 hours, 7 days
E-mailEngineer reply within 8 working hoursMonday – Saturday
Spare parts (stock items)Dispatched within 48 hoursMonday – Saturday
Commissioning supportRemote walk-through scheduled within 3 daysBy appointment

Frequently asked questions

Why is there frost on my compressor?
Frost usually means the evaporating temperature has dropped too low. The common causes are an undercharge or a slow leak, restricted airflow across the evaporator, a TXV stuck open, or heavy infiltration from door traffic. Measure superheat at the compressor suction: below 3 K points to a flooded evaporator, above 10 K to a starved one. Never simply add refrigerant — find the cause first. See document CX-TC-001.
How do I know if the system is overcharged?
High subcooling (above 8 K), high discharge pressure and a high condensing approach all point to overcharge. Overcharging does not add capacity — it raises energy consumption and risks liquid slugging that damages valves, pistons and bearings. Charge by superheat (fixed orifice) or subcooling (TXV), never by sight glass alone. See document CX-TC-002.
What superheat and subcooling should I expect?
At design load: suction superheat 5–8 K at the evaporator outlet, liquid subcooling 4–8 K at the liquid line. The condensing approach (condensing temperature minus ambient) should sit around 8–15 K. If any of these drifts more than 10% from the commissioning sheet, that is the trigger for investigation. See document CX-TC-009.
My frozen room takes far too long to pull down after defrost.
Check three things in this order: whether defrost terminates on coil temperature or only on time; whether the drain pan and drain line are clear and heat-traced; and whether the fan-delay setting is long enough for residual water to drain. A blocked drain is the most common cause of a coil that "has lost capacity". See documents CX-TC-007 and CX-TC-010.
How often should the condenser be cleaned?
Monthly in dusty or high-traffic environments, quarterly in clean locations. Clean from the inside out, against normal airflow, with low-pressure water and a suitable detergent — never with a high-pressure jet, which flattens the fins permanently. Log the condensing pressure before and after so the improvement is measurable. See document CX-TC-009.
Can I just top up the refrigerant without finding the leak?
No. A system that needs refrigerant every season is leaking, and topping up simply repeats the failure while raising energy cost and environmental impact. Locate and repair the leak, replace the filter drier, then evacuate to below 500 microns and recharge by weight. See document CX-TC-008.
Which refrigerant replaces R404A?
R448A or R449A are the most common non-flammable retrofit options, with capacity close to R404A and no major component change. Expect a higher discharge temperature and mass flow, so verify POE oil compatibility and replace the filter drier. For new low-temperature plant, CO₂ and ammonia systems are increasingly the better long-term choice. See document CX-TC-006.
Do you support systems that CHANGXUE did not supply?
We help with the refrigeration side of any cold-store, whatever the brand of condensing unit. Send the nameplate photo and your readings through the form below and an engineer will advise on the most likely cause and the parts required.

Request technical support

Send us your readings

The more of the following you can include, the faster we can isolate the fault:

  • Equipment model and serial number (nameplate photo is ideal)
  • Suction and discharge pressure, and the corresponding temperatures
  • Room temperature and the setpoint it should hold
  • Suction superheat and liquid subcooling, if available
  • When the fault appears — on start-up, at night, after defrost, at full load
  • Any recent work: gas top-up, component replacement, panel repair

Requests submitted here reach the same engineering inbox as the hotline, and are logged so that a recurring fault is visible on the second call rather than the fifth.

Technical Support / Repair Request

Fields marked * are required. You will receive a confirmation by e-mail.